Question about Art Cool LA181CNW Split System Air Conditioner
...pressed but does not run. a code "CH" alternating with "46" is shown in the LCD lower right panel CH46 indicates that the suction pipe sensor is missing or
Question about Art Cool LA181CNW Split System Air Conditioner
...We have an LG Split System with a Remote Touch Screen Control Panel. There is a message flashing "CH46". How do we fix
Question about Art Cool LA181CNW Split System Air Conditioner
panasonic SA CH46 double cassette reciver not workimg panasonic SA CH46 double cassette reciver not working. system is in stand by mode not getting on pressing fuction button . I HAVE A PROBLEM IN ...
Question about Art Cool LA181CNW Split System Air Conditioner
Hello! The error code is CH46 (LG split klima). Why is this happened? Thank you! WHERE SHOULD THE SUCTION PIPE SENSOR BE CH46 indicates that the suction pipe sensor is missing orfaulty. If misplaced, ...
Question about LS240CE Split System Air Conditioner
My inside unit has an error code flashing ch46 do you have a list of codes and what they mean. CH-46.Outdoor unit suction sensor fault. Disconnect from PCB and measure resistance. 10 kOhm at 10°C
what does ch 46 mean on the led display and how do I fix it so the airconditioner will stay on CH46 indicates that the suction pipe sensor is missing or faulty. Check with your sensor and replace it, ...
It keeps turning itself off and on the display it flashes CH,46 CH46 indicates that the suction pipe sensor is missing orfaulty. Check the sensor may be misplaced or circuit open. If opened replace it
Question about LS240CE Split System Air Conditioner
operation lamp showing - error CH 46 - unit not operating CH46 Outdoor unit suction sensor fault. Disconnect from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C. If OK ...
ERROR CH46 if you have multiple unit running from one compressor then you get this code when you set one unit to heat and another unit to cool. All units running from a single compressor need to be in
Question about LSC121PMA Split System Air Conditioner
How do I locate the correct resistor for error ch46 Outdoor unit suction sensor fault. Disconnect from PCB and measure resistance. 10 kOhm at 10°C and 4 kOhm at 30°C. If OK replace PCB, if not replace